Home Store Data Loggers / Power Analysers Chauvin Arnoux PEL 106 Power Energy Logger
Chauvin Arnoux PEL 106 Power Energy Logger
£2,459.00 Ex VAT
Chauvin Arnoux PEL106 Power Energy Logger
The Chauvin Arnoux PEL106 Power Energy Logger is an exceedingly well-constructed piece of kit designed to be suitable for all types of electrical networks and ideal for installation on electricity poles. The PEL 106 includes 4 voltage inputs & 4 current inputs, will automatically recognise the sensors connected and vitally, can be operated without having to cut off the mains power supply. Recording continuously with only a brief interval of 200ms between each measurement, this power logger measures and records all the relevant data for energy consumption diagnostics. Capable of 5 readings per second and recorded simultaneously on each phase, all data is captured as per the IEEE 1459 standard. Thanks to vast measurement ranges, voltage up 1,000 VAC/VDC and current up to 10 kVAC / 5 kVDC, the PEL 106 can log power values up to 10 GW/GVar/GVA, and energy up to 4 EWh/EVAh/EVarh.
The PEL106 Power Energy Logger performs the following measurements:
- RMS and DC measurements with 128 samples/cycle – simultaneously on each phase
- AC and/or DC voltages up to 1000 V
- Current up to 10 kA AC or 5 kA DC (depending on the current sensor)
- Energy values up to 4 EWh / 4 EVAh / 4 EVarh & total energy (4 quadrants)
- Phase data: cos φ, tan Φ, power factor (PF)
- Crest factor
- Harmonics up to the 50th order for currents and voltages
- DC, 50 Hz, 60 Hz and 400 Hz measurements
Chauvin Arnoux and the PEL106 are committed to improving energy efficiency within economical, sustainable buildings. Optimising energy consumption is crucial to meet the latest regulatory requirements and with a dedicated Power Energy Logger, users can perform energy efficiency projects & directly oversee electrical distribution systems. A correctly positioned PEL106 will quickly isolate areas in need of maintenance and show whether applied solutions have been successful. When attached to different electrical feeders these units will size the relative weight of each line in terms of overall consumption, define a load profile for the installation and then prioritise the improvements which must be made.
Key Features
- Suitable for all types of electrical networks
- Ideal for installation on electricity poles
- Provides real-time oversight
- Automatically recognises connected sensors
- 4 voltage inputs and 4 current inputs
- Operates without having to cut off mains power supply
- Measures/records all energy consumption diagnostics data
- Interval of 200ms between each measurement
- 5 readings per second recorded simultaneously on each phase
- Voltage range up 1,000 VAC/VDC
- Current range up to 10 kVAC / 5 kVDC
- Log power values up to 10 GW/GVar/GVA
- Log energy up to 4 EWh/EVAh/EVarh
- RMS and DC measurements with 128 samples/cycle – simultaneously on each phase
- AC and/or DC voltages up to 1000 V
- Phase data functions: cos φ, tan Φ, power factor (PF)
- THD calculation for currents and voltages
- Harmonics up to the 50th order for currents and voltages
- DC, 50 Hz, 60 Hz and 400 Hz measurements
- Analogue measurements for identifying external parameters
- 2 x 4 analogue channels compliment the voltage, current and power measurements
- Ideal for applications involving renewable energies
- Suitable for workshop, factory, agency or building environments
- Recordings are all time & date stamped
- Built-in customisable Alarm mode
- Large SD card ideal for lengthy measurement campaigns.
- Communication modes; WiFi, 3G-UMTS/GPRS, LAN (Ethernet), Bluetooth, USB ports
- Monitor measurements & recover data from anywhere in the world
- Insert a SIM card for remote connection via a GSM 3G link
- IRD server emails user should an alarm be triggered
- Use the IRD server to view measurements remotely via the internet
- Compatible with FREE multilingual Android App
- Communicate via Bluetooth with the device through smart device
- Built-in software sensor enables measurements for applications on motors
- Motor measurements; rotation speed, torque & engine efficiency
- Wi-Fi interface for PC access
- PEL Transfer software analyses data and calculates cost of power consumed Software results displayed in selected currency
- DataView processing software creates certified or customised reports
- Self-powered via its voltage inputs up to 1000 V
- Backlit LCD screen with triple digital display
- Compact magnetised casing, extremely portable
- No impact on electrical cabinets
- Data recorded as per the IEEE 1459 standard
- Rated IP67, 1000V CAT IV
Comparison Chart
Chauvin Arnoux PEL Series Comparison Table
|
PEL 102 |
PEL 103 |
PEL 104 |
PEL 106 |
Installation Type |
Single-phase, split-phase, three-phase (with or without neutral) |
Number of Channels |
4V & 3A with calculated nutral current |
5V & 4A |
Acquistion Speed |
1s |
1s |
200ms |
200ms |
Calculated Powers |
P, Q & S |
P, Q & S |
P, N, S, Q1 & D |
P, N, S, Q1 & D |
Total or Partial Energy |
✔ |
✔ |
✔ |
✔ |
Display by Quadrants |
✔ |
✔ |
✔ |
✔ |
Energy Cost Calculation |
✔ |
✔ |
✔ |
✔ |
Energy Lost Calculation |
– |
– |
✔ |
✔ |
Motor Rotation Speed |
✔ |
✔ |
✔ |
✔ |
Motor Torque |
✔ |
✔ |
✔ |
✔ |
Motor Efficiency |
✔ |
✔ |
✔ |
✔ |
Bluetooth, Ethernet & USB |
✔ |
✔ |
✔ |
✔ |
4-Line Backlit LCD Screen |
– |
✔ |
✔ |
✔ |
Wi-Fi |
– |
– |
✔ |
✔ |
3G & GPRS |
– |
– |
✔ |
✔ |
Alarms/Reports by Email |
– |
– |
✔ |
✔ |
Max. SD Card Memory |
32Gb |
32Gb |
32Gb |
32Gb |
Self Powering Adaptor |
Optional |
Optional |
Included |
Built-In |
External Analogue Inputs |
– |
– |
8 using L452 |
8 using L452 |
Ingress Protection |
IP54 |
IP54 |
IP54 |
IP67 |