Tech Specs
Fluke 1600 Series Technical Specifications
AC/DC Voltage (TRMS) | ||||
---|---|---|---|---|
Range | Resolution | Input Impedance | Overload Protection | |
500V | 0.1V | 3.3MΩ | 660V rms | |
Continuity Testing (Rlo) | ||||
Range (Autoranging) | Resolution | Open Circuit Voltage | ||
20Ω | 0.01Ω | >4V | ||
200Ω | 0.1Ω | |||
2000Ω | 1Ω | |||
Insulation Resistance Measurement (Riso) | ||||
Model Number | Test Voltages | |||
1662 | 100, 250, 500 and 1000V | |||
1663/1664 FC | 50, 100, 250, 500 and 1000V | |||
Test Voltage | Insulation Resistance Range | Resolution | Test Current | |
50V | 20MΩ/50MΩ | 0.01MΩ/0.1MΩ | 1mA @ 50kΩ | |
100V | 20MΩ/100MΩ | 0.01MΩ/0.1MΩ | 1mA @ 100kΩ | |
250V | 20MΩ/200MΩ | 0.01MΩ/0.1MΩ | 1mA @ 250kΩ | |
500V | 20MΩ/200MΩ/500MΩ | 0.01MΩ/0.1MΩ/1MΩ | 1mA @ 500kΩ | |
1000V | 20MΩ/200MΩ/1000MΩ | 0.01MΩ/0.1MΩ/1MΩ | 1mA @ 1MΩ | |
Insulation Pretest | ||||
Insulation Safety Pretest | Requires the unit to be connected to L, N and PE | |||
Loop and Line Impedance (Zi) | ||||
Range | Resolution | |||
10Ω (Hi current mΩ mode) 20Ω/200Ω/2000Ω | 1mΩ / 0.01Ω / 0.1Ω / 1Ω | |||
RCD Testing | ||||
Model Number | Types Tested | |||
1662 | AC, G, S, A/F | |||
1663/1664 FC | A/F, AC, B/B+, G and S | |||
RCD Trip Time Test (ΔT) | ||||
Current Range | Step Size | Dwell Time | Measurement Accuracy | |
Type G | Type S | |||
30 to 110% of RCD Rated Current | 10% of index IΔN | 300ms/step | 500ms/step | ±5% |
Notes 30 % to 210 % for Type A IΔN = 10mA 20 % to 210 % for Type B |
Specified trip current ranges (EN 61008-1): 50 % to 100 % for Type AC 35 % to 140 % for Type A (>10 mA) 35 % to 200 % for Type A (≤10 mA) 50 % to 200 % for Type B |
|||
Earth Resistance Test (RE) – Only Available On 1664 FC and 1663 | ||||
Range | Resolution | Frequency | Output Voltage | |
200Ω | 0.1Ω | 128Hz | 25V | |
2000Ω | 1Ω | 128Hz | 25V | |
Phase Sequence Indication | ||||
Icon | Range | Display | ||
Shows icon when active | 100 to 500V | 1-2-3 or 3-2-1 | ||
General Specifications | ||||
Dimensions | 10cm (L) x 25cm (W) x 12.5cm (H) | |||
Weight (Including Batteries) | Approx 1.3kg | |||
Battery Size | 1.5V type AA (IEC LR6) x 6 | |||
Sealing | IP40 | |||
Safety | Complies with IEC/EN61010-1, UL61010, ANSI/ISA – s82.02.01 and CAN/CSA c22.2 No. 1010 | |||
Overvoltage | CAT III 500V, CAT IV 300V | |||
Performance | EC/EN61557-1 to IEC/EN61557-7 and IEC/EN61557-10 |
Reviews